Week's Topic: Thermal Load: the Six Components

Thermal Load: the Six Components

A poorly sized chamber cannot be fixed with more refrigerant. It falls short in summer, cycles excessively or freezes the evaporator. The cause is usually in the load calculation. These are the six components you need to add up.

1. Heat Transmission through Walls, Roof and Floor

This is the heat that enters through the insulation. It depends on the surface area, thickness and thermal conductivity of the panel, and the temperature difference with the outside. Typical error: forgetting that a wall in the sun or next to a warm chamber does not experience the ambient temperature. And the floor also counts.

2. Product

This is usually one of the largest items. It includes:

Ask the customer how much enters per day and at what temperature it arrives. Without that data, the calculation is just an assumption.

3. Air Infiltration and Renewal

Every time the door opens, warm humid air enters. It must be cooled and dehumidified. The door size, frequency of opening and whether there is a curtain or antechamber matter. In freezer chambers, that humidity ends up as frost on the evaporator.

4. Personnel

Each operator contributes sensible and latent heat. It depends on how many work inside and for how long. In a storage chamber it is small. In a cutting or preparation room it becomes significant.

5. Lighting

All the electrical power of the luminaires ends up as heat inside the chamber. With LED it drops a lot, but it is not zero. Also count the actual operating hours, not just the installed power.

6. Fans and Defrosting

The evaporator motors dissipate their power inside the enclosure. If defrosting is electric, the resistors add load and force temperature recovery afterwards. This item depends on the evaporator chosen, so the calculation is iterated: load, evaporator, corrected load.

After Adding Up: from Calculation to Selection

If it is a retrofit, recalculate the capacity with the new gas. According to Systcold's theoretical calculation, switching from R-402A to R-448A in the same compressor means about −8 % capacity in medium temperature and between −13 and −14 % in low temperature. A chamber that was running tight may no longer comply. And no HFC or HFO is "drop-in" without reviewing valve, oil and superheat.

Do the thermal load calculation with the Systcold JDC thermal load tool. Then, select unit, evaporator and valve with manufacturer data in the same environment.

Industry Developments

Systcold JDC technical summary from 14/11/2026 to 15/11/2026. All figures come from manufacturer catalogues loaded in the database.

The Database Today

New or Updated Technical Datasheets

Gas of the Month: R-32

HFC (Difluoromethane) · ASHRAE A2L · GWP 675 · ODP 0.

Direct replacements: —.

With adjustment: R-410A (similar pressures).

Regulations: Approved; low GWP; slight flammability A2L.

Complete R-32 datasheet

Featured Compressor: MANEUROP (Danfoss) MPT / MPTS Series (Tandem)

32 models in the database. Manufacturer oil: POE ISO 68 (100 % of models). Gases: R-507A, R-404A. Power: 3/8–2/3 HP.

Complete datasheet

Complete and free technical catalogue: systcoldjdc.com/gases · Datasheets: systcoldjdc.com/gases/fichas

```

▶ Systcold JDC videos and news: YouTube · Facebook · Instagram · Telegram

Have a refrigeration question? Ask the Assistant
Catalog-based answers, free.
Ask the Assistant

▶ This bulletin's video: YouTube · Facebook · Instagram · Telegram

Sources: Tabla de gases refrigerantes de Systcold JDC (revisada) · Fichas de compresor MANEUROP (Danfoss) MPT / MPTS Series (Tándem) (catálogo del fabricante) · TEMA 13: Carga térmica: los seis componentes · coolingpost.com: https://www.coolingpost.com/ · coolingpost.com: https://www.coolingpost.com/world-news/danfoss-injector-boosts-co2-refrigeration/

← Technical newsletter

Get the newsletter by email

Double opt-in by email. One-click unsubscribe in every issue.