Refrigerant regulation for installers

Free information for installers: which gases can no longer be recharged, how much each kilo costs in tax, which gas to change to and what must be readjusted in the system. Every legal statement has its source; capacity figures are theoretical (CoolProp) and do not replace manufacturer data.

Reviewed on 25/10/2026

EU Regulation 2024/573 timeline

1/1/2025 · Refrigeration: servicing and maintenance with virgin gas of GWP ≥ 2500 is banned, whatever the charge. Recovered or recycled gas (labelled, used by the company that recovered it) is allowed until 1/1/2030.
1/1/2026 · Air conditioning and heat pumps: servicing with virgin gas of GWP ≥ 2500 is banned. Recovered or recycled gas allowed until 1/1/2032.
1/1/2032 · Refrigeration (except chillers): servicing with virgin gas of GWP ≥ 750 is banned.
12/3/2027 · Certification: the certificate obligation for companies applies from this date. Certificates also cover CO₂, ammonia and hydrocarbons (types A1, A2, B, C, D, E).
12/3/2029 · Holders of Regulation 517/2014 certificates must complete a refresher course or assessment. Recertification at least every 7 years.

Gases, safety class, GWP and Spanish tax

Spanish fluorinated gas tax (Law 16/2013, amended by Law 7/2022): €0.015 × GWP per kg, capped at €100/kg; gases with GWP ≤ 150 are not taxed. Indicative amount: always check current law.

GasClassGWPTax €/kgStatus
R-22 📈A1181027,15Prohibido producción países Anexo I; fase out global
R-134a 📈A1143021,45Restringido UE F-Gas 2024; fase out gradual global
R-404A 📈A1/A2L392258,83Alto GWP; prohibido equipos nuevos UE desde 2022
R-410A 📈A1208831,32Prohibido nuevos sistemas residenciales UE 2025
R-507A 📈A1398559,78Prohibido equipos nuevos UE; mismo GWP ~4000
R-32 📈A2L67510,13Aprobado; bajo GWP; ligera inflamabilidad A2L
R-448A 📈A1138720,81Aprobado; GWP inferior; recomendado por UE
R-449A 📈A1139720,96Aprobado; cumple F-Gas UE fase 1
R-452A 📈A2L214132,12Aprobado con precauciones A2L
R-407C 📈A1177426,61GWP alto; restricciones futuras UE
R-717 📈B2L00,00Sin restricciones GWP; ATEX requerido
R-744 📈A110,00Transcrítico: alta presión (>120 bar); regulación favorable
R-600a 📈A330,00Inflamable clase A3; cantidades ≤150g
R-290 📈A330,00Inflamable clase A3; cantidades ≤500g HVAC
R-513A 📈A16319,47Aprobado; GWP~630; recomendado por UE
R-454B 📈A2L4666,99Aprobado equipos nuevos; Honeywell Solstice® 454B
R-1234yf 📈A2L40,00Obligatorio automoción UE desde 2017
R-1234ze 📈A2L70,00Aprobado chillers alta eficiencia
R-422D 📈A1272940,94Obsolescencia gradual; GWP alto
R-417A 📈A1234635,19Obsolescencia gradual; GWP alto

Substitutes and capacity loss

Same compressor (same swept volume). Medium temperature: Te −10 / Tc 45 °C; low: Te −35 / Tc 40 °C; 10 K superheat; Te and Tc at dew point (EN 12900 catalogue convention). For gliding blends, if condensing is measured at bubble point the real loss can be 4–6 points higher. Theoretical Systcold calculation with CoolProp.

ChangeTypeCapacity MTCapacity LTDischarge MTWhat to readjust
R-22 → R-407C A1Indirect (changes required) -9 % -18 % -10 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: change to POE (R-22 systems usually use MO/AB)
  • Equipment label and log with the new gas and charge
R-134a → R-513A A1Direct (drop-in) +1 % +4 % -6 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Equipment label and log with the new gas and charge
R-134a → R-1234yf A2LIndirect (changes required) -6 % -3 % -10 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Becomes A2L: see safety requirements below
  • Equipment label and log with the new gas and charge
R-404A → R-448A A1Direct (drop-in) +1 % -2 % +9 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -8 %)
  • Discharge temperature +9 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-404A → R-449A A1Direct (drop-in) +1 % -2 % +8 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -8 %)
  • Discharge temperature +8 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-404A → R-452A A2LDirect (drop-in) -1 % -3 % +0 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Equipment label and log with the new gas and charge
R-410A → R-32 A2LIndirect (changes required) +13 % +15 % +22 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Discharge temperature +22 K: watch compressor limit
  • Becomes A2L: see safety requirements below
  • Equipment label and log with the new gas and charge
R-410A → R-454B A2LIndirect (changes required) -2 % -2 % +6 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -8 %)
  • Discharge temperature +6 K: watch compressor limit
  • Becomes A2L: see safety requirements below
  • Equipment label and log with the new gas and charge
R-507A → R-448A A1Direct (drop-in) +0 % -5 % +10 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -10 %)
  • Discharge temperature +10 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-507A → R-452A A2LDirect (drop-in) -3 % -6 % +0 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -6 %)
  • Becomes A2L: see safety requirements below
  • Equipment label and log with the new gas and charge
R-507A → R-449A A1Indirect (changes required) -1 % -5 % +9 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -11 %)
  • Discharge temperature +9 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-449A → R-448A A1Indirect (changes required) +0 % +0 % +1 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Equipment label and log with the new gas and charge
R-452A → R-448A A1Indirect (changes required) +3 % +1 % +9 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Discharge temperature +9 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-422D → R-22 A1Direct (drop-in) +24 % +38 % +23 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Discharge temperature +23 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-422D → R-407C A1Indirect (changes required) +12 % +14 % +13 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Discharge temperature +13 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-422D → R-417A A1Indirect (changes required) -9 % -11 % +1 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure -13 %)
  • Equipment label and log with the new gas and charge
R-417A → R-22 A1Direct (drop-in) +36 % +54 % +22 K
  • Expansion valve: readjust superheat
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure +13 %)
  • Discharge temperature +22 K: watch compressor limit
  • Equipment label and log with the new gas and charge
R-417A → R-407C A1Indirect (changes required) +23 % +27 % +13 K
  • Expansion valve: check orifice/element for the new gas
  • Oil: POE, confirm with the compressor manufacturer
  • Pressure switches: readjust (condensing pressure +14 %)
  • Discharge temperature +13 K: watch compressor limit
  • Equipment label and log with the new gas and charge

A2L refrigerants as a solution

FAQ

How much capacity do I lose changing R-22 to R-407C?
With the same compressor, the theoretical Systcold calculation gives -9 % at medium temperature and -18 % at low temperature.
How much capacity do I lose changing R-134a to R-513A?
With the same compressor, the theoretical Systcold calculation gives +1 % at medium temperature and +4 % at low temperature.
How much capacity do I lose changing R-134a to R-1234yf?
With the same compressor, the theoretical Systcold calculation gives -6 % at medium temperature and -3 % at low temperature.
How much capacity do I lose changing R-404A to R-448A?
With the same compressor, the theoretical Systcold calculation gives +1 % at medium temperature and -2 % at low temperature.
How much capacity do I lose changing R-404A to R-449A?
With the same compressor, the theoretical Systcold calculation gives +1 % at medium temperature and -2 % at low temperature.
How much capacity do I lose changing R-404A to R-452A?
With the same compressor, the theoretical Systcold calculation gives -1 % at medium temperature and -3 % at low temperature.
How much Spanish tax does R-22 pay?
€27.15 per kg (€0.015 × GWP 1810).
How much Spanish tax does R-134a pay?
€21.45 per kg (€0.015 × GWP 1430).
How much Spanish tax does R-404A pay?
€58.83 per kg (€0.015 × GWP 3922).
How much Spanish tax does R-410A pay?
€31.32 per kg (€0.015 × GWP 2088).

Sources

See also: Technical compressor catalogue · FAQ · Boletín / Newsletter